Page 1 of 18Issue 1234507120-01This is a safety alert symbol and should never be ignored. When you see this symbol on labels or inmanuals, be alert t
Issue 1234 507120-01Page 10 of 18Make sure the liquid line and suction line entry points aresealed with either Armaflex material or with Permagum.Perm
Page 11 of 18Issue 1234507120-01Figure 12Low Voltage Connections (3-Speed PSC Motor)
Issue 1234 507120-01Page 12 of 18Airflow - Cooling Blower SpeedThe cooling blower speed is factory configured to providecorrect airflow for an outdoor
Page 13 of 18Issue 1234507120-01Check-out ProceduresNOTE: Refer to outdoor unit installation instructions forsystem start-up instructions and refrig
Issue 1234 507120-01Page 14 of 18MaintenanceDo not operate system without a filter. A filter isrequired to protect the coil, blower, and internal par
Page 15 of 18Issue 1234507120-01Start-Up and Performance Checklist (Horizontal Configuration)Figure 14
Issue 1234 507120-01Page 16 of 18Figure 15Start-Up and Performance Checklist (Upflow Configuration)
Page 17 of 18Issue 1234507120-01ALLIED AIR ENTERPRISESEQUIPMENT LIMITED WARRANTYAPPLIES IN U.S.A. AND CANADA ONLYFAILURE TO MAINTAIN YOUR EQUIPMENT WI
Issue 1234 507120-01Page 18 of 18Allied Air Enterprises Inc. (“Allied Air”) provides its air conditioning and heating products with a Standard Limite
Issue 1234 507120-01Page 2 of 18GENERALton, 96W38 for the 2 and 2.5 ton, 97W95 for the 3 ton, and97W96 for the 3.5 through 5 ton). All units may be
Page 3 of 18Issue 1234507120-01RequirementsExcessive Weight Hazard - Use two or more peoplewhen moving and installing the unit. Failure to do socan re
Issue 1234 507120-01Page 4 of 18Installation ClearancesNON-DUCTED RETURN CLOSET INSTALLATIONThe air handler can be installed in a closet with a falseb
Page 5 of 18Issue 1234507120-01NOTE: When the unit is installed in horizontal applications,a secondary drain pan is recommended. Refer to localcode
Issue 1234 507120-01Page 6 of 183. Remove coil assembly, bottom drain pan and horizontaldrain pan as one assembly from the air handler.4. Move the hor
Page 7 of 18Issue 1234507120-01On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in th
Issue 1234 507120-01Page 8 of 18The air handler is provided with 3/4” NPT condensate drainconnections.Sloping the DrainMake sure the unit is sloped (s
Page 9 of 18Issue 1234507120-01Supply and return duct system must be adequately sizedto meet the system’s air requirements and static pressurecapabili