This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
NOTE: These instructions are intended as a general guide and
do not supersede national, state or local codes in any way.
These instructions must be left with the property owner.
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFCs, HCFCs and HFCs) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
CAUTION
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury
or loss of life. Installation and service must be performed
by a licensed professional installer (or equivalent), service
agency or the gas supplier.
WARNING
Shipping and Packing List
Package 1 of 1 contains the following:
1 - Assembled air handler unit for upflow or horizontal air
discharge application (includes upflow and horizontal
drain pans and pre-installed air filter).
Check equipment for shipping damage. If found,
immediately report damage to the last carrier. Check the
unit rating plate to confirm that delivered unit matches
order.
TABLE OF CONTENTS
Shipping and Packing List ........................................................ 1
Unit Dimensions ....................................................................... 2
Requirements ........................................................................... 3
Installation Clearances ............................................................. 3
Installation................................................................................. 4
Condensate Drain ..................................................................... 7
Duct Systems and Filters ......................................................... 8
Connecting Refrigerant Lines ................................................... 9
Sealing the Unit ........................................................................ 9
Electrical Connections ............................................................ 10
Airflow - Cooling Blower Speed .............................................. 12
Check - Out Procedures ......................................................... 13
Operation ................................................................................ 13
Maintenance ........................................................................... 14
Cabinet Insulation ................................................................... 14
Warranty ................................................................................. 17
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you to
fiberglass wool. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California to
cause cancer.)
Fiberglass wool may also cause respiratory, skin, and
eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
WARNING
INSTALLATION INSTRUCTIONS
BCE3M & BCS3M SERIES AIR HANDLER
These instructions must be read and understood completely before attempting installation.
0659373-80 Version B
Manufactured By
Advanced Distributor Products
A Lennox International, Inc. Company
1995 Air Industrial Park Road
Grenada, MS 38901
(P) 507120-01
*P507120-01*
Vue de la page 0
1 2 3 4 5 6 ... 17 18

Résumé du contenu

Page 1 - INSTALLATION INSTRUCTIONS

Page 1 of 18Issue 1234507120-01This is a safety alert symbol and should never be ignored. When you see this symbol on labels or inmanuals, be alert t

Page 2

Issue 1234 507120-01Page 10 of 18Make sure the liquid line and suction line entry points aresealed with either Armaflex material or with Permagum.Perm

Page 3

Page 11 of 18Issue 1234507120-01Figure 12Low Voltage Connections (3-Speed PSC Motor)

Page 4

Issue 1234 507120-01Page 12 of 18Airflow - Cooling Blower SpeedThe cooling blower speed is factory configured to providecorrect airflow for an outdoor

Page 5

Page 13 of 18Issue 1234507120-01Check-out ProceduresNOTE: Refer to outdoor unit installation instructions forsystem start-up instructions and refrig

Page 6

Issue 1234 507120-01Page 14 of 18MaintenanceDo not operate system without a filter. A filter isrequired to protect the coil, blower, and internal par

Page 7

Page 15 of 18Issue 1234507120-01Start-Up and Performance Checklist (Horizontal Configuration)Figure 14

Page 8

Issue 1234 507120-01Page 16 of 18Figure 15Start-Up and Performance Checklist (Upflow Configuration)

Page 9

Page 17 of 18Issue 1234507120-01ALLIED AIR ENTERPRISESEQUIPMENT LIMITED WARRANTYAPPLIES IN U.S.A. AND CANADA ONLYFAILURE TO MAINTAIN YOUR EQUIPMENT WI

Page 10 - WARNING

Issue 1234 507120-01Page 18 of 18Allied Air Enterprises Inc. (“Allied Air”) provides its air conditioning and heating products with a Standard Limite

Page 11 - Figure 12

Issue 1234 507120-01Page 2 of 18GENERALton, 96W38 for the 2 and 2.5 ton, 97W95 for the 3 ton, and97W96 for the 3.5 through 5 ton). All units may be

Page 12

Page 3 of 18Issue 1234507120-01RequirementsExcessive Weight Hazard - Use two or more peoplewhen moving and installing the unit. Failure to do socan re

Page 13 - Operation

Issue 1234 507120-01Page 4 of 18Installation ClearancesNON-DUCTED RETURN CLOSET INSTALLATIONThe air handler can be installed in a closet with a falseb

Page 14 - IMPORTANT

Page 5 of 18Issue 1234507120-01NOTE: When the unit is installed in horizontal applications,a secondary drain pan is recommended. Refer to localcode

Page 15 - Figure 14

Issue 1234 507120-01Page 6 of 183. Remove coil assembly, bottom drain pan and horizontaldrain pan as one assembly from the air handler.4. Move the hor

Page 16 - Figure 15

Page 7 of 18Issue 1234507120-01On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in th

Page 17 - ALLIED AIR ENTERPRISES

Issue 1234 507120-01Page 8 of 18The air handler is provided with 3/4” NPT condensate drainconnections.Sloping the DrainMake sure the unit is sloped (s

Page 18

Page 9 of 18Issue 1234507120-01Supply and return duct system must be adequately sizedto meet the system’s air requirements and static pressurecapabili